Second, install the issues that should be noted. Check whether the casing type is correct, whether the electrical test oil test is qualified; check whether the oil level of the casing is suitable, whether there is oil leakage or porcelain sleeve damage; check whether the lead length is suitable, wipe the casing clean, check the welding condition of the lead wire The installation of the casing shall comply with the lifting operation regulations, and the transformer skeleton shall be prevented from colliding and damaging the porcelain sleeve. The inclination of the casing lifting shall be determined according to the angle of the riser of the transformer skeleton casing, and the string of the pulling lead shall be strong and hung in the appropriate position. As the bushing is installed, the lead head is gradually pulled out, and the lead wire must not be hung or knotted. If the lead wire cannot be lifted, the cause should be ascertained, and the force cannot be pulled or pulled with a spreader; the tapered insulation of the lead wire If it is damaged, it should be re-wrapped; the lead and terminal should have sufficient contact area and contact pressure. The terminals must be reliably sealed to prevent water ingress.

Again, the overhaul should be noted. Place the casing vertically on the bracket, remove the tail pressure equalizing cover, and release the oil from the tail oil plug; first remove the ground small sleeve, then remove the terminal seat washer, remove the expander; support the casing with the bracket Brake the end of the brass tube, tighten the spring pressure plate nut to compress the spring. When the fastening nut on the conductive tube is separated from the spring pressure plate, remove the fastening nut, and then remove the spring pressure plate, spring, spring seat and porcelain sleeve. Hang the brass tube, remove the tail bracket, lift the lower porcelain sleeve, remove the base, then drop the porcelain sleeve, and hang the capacitor core; reassemble the opposite of the above sequence, after assembly, put vacuum immersion oil, strictly in accordance with the process The procedure is carried out.

Finally, the problem that the transformer skeleton related operators should pay attention to. Check the pre-test personnel, when disconnecting the small casing lead wire, prevent the guide rod from rotating or breaking the grounding lead. After the test, the original condition shall be restored; after the operation of the oil sample personnel, the sampling block shall be tightened; the personnel of the lead wire shall be disassembled, and the upper and lower casings shall be prevented from being mistakenly stepped on the final screen; the maintenance personnel shall observe the oil level of the casing and timely replenish the oil.

Third, specific measures

The main reasons for the formation of casing defects are: first, due to product quality problems or improper maintenance methods; second, because the casing is not completely vacuumed during the factory or overhaul, so that the air remains in the casing screen; the third is due to the quality of the rubber pad. Off or super-period operation makes the rubber pad aging; Fourth, the casing structure is unreasonable; Fifth, the contact resistance of the wire connection part is large, causing local overheating.

After formulating corresponding countermeasures, we can formulate specific measures from the main defects:

Unqualified casing oil sample, including acetylene gas and other defects. The measures taken are: strict inspection of new casings to avoid failure caused by human factors.

In case of poor sealing of the casing, there is an ingress or oil leakage phenomenon. The measures taken by the transformer skeleton are: to maintain the seal by replacing the rubber pad, so that the casing has no leakage.

Defects such as overheating of the casing head. The specific measures can be changed into copper-copper contact by changing copper-aluminum to reduce oxidation. In addition, in the process of disassembly, connection and introduction, it is necessary to check whether the parts are well connected.

Mobile website

Mobile website

Get product solutions

Contact information

Address: No. 4, Yangguang Road,
Shanwu Yangguang Industrial
Zone, Shijie Town, Dongguan
Contact: Mr Zhang / +86 13763271520
Tel: +86 0769-86388745
COPYRIGHT @ Dongguan pinye Electronics Co., Ltd
Technical Support: 【Dongguan Website Construction】 【administer】